5
 - 28
5.4 Using the Preset Function
 
5
FUNCTIONS
(2) Operation when presetting by the external control signal
Apply ON voltage to the preset input terminal (PRST) for external input to execute 
preset. Operation example is indicated in Figure 5.13.
Figure 5.13 Operation example of the preset function by external control signal
POINT
When the external preset request detection (X08) is OFF, both the preset 
command (Y04) and the preset input terminal (PRST) are valid.
Table 5.11 Details of operation example of the preset function by external control signal
Number
Description
1)
Write any value in the preset value setting (Un\G4 and 5) of the QD64D2 in 32-
bit binary format.
2)
When the preset input terminal (PRST) is turned from OFF to ON, the preset 
value setting (Un\G4 and 5) is stored in the present value (Un\G12 and 13). 
The preset can be executed regardless of ON/OFF status of the count enable 
command (Y06).
3)
While the external preset request detection (X08) is ON, the preset cannot be 
executed by turning ON the preset command (Y04) or the preset input terminal 
(PRST).
4)
When the external preset request detection reset command (Y08) is turned ON 
and the external preset request detection (X08) turns OFF, the preset can be 
executed.
*t   2ms
ON
OFF
ON
OFF
ON
OFF
2001
2000
0
1067
1066
1065
1002
1001
1000
ON
OFF
2000
0
1)
3)
3)
2)
2)
2)
4)
t*
t*
t*
t*
2023 2024
2025 2000
2001
ON
OFF
1000
1)
t*
Count enable command 
(Y06)
Counter input pulse
Preset value setting 
(Un\G4 and 5)
Preset command 
(Y04)
Preset input terminal 
(PRST)
External preset 
request detection 
(X08)
External preset request 
detection reset command 
(Y08)
Present value 
(Un\G12 and 13)
to
to