Справочник Пользователя для Siemens 9300

Скачать
Страница из 176
Data and Event Logging
 9300 Series User’s Guide
Page 126
Chapter 5 - Features and Applications 
Data and Event Logging 
The meter includes powerful data logging (9330 and 9350 meters only) and event 
recording capabilities. Data and event logs recorded by the meter are prioritized 
and stored onboard. Data is retrieved periodically by the WinPM.Net software Log 
Server (or other third party application). 
If you use WinPM.Net software, all retrieved data from your system is stored in an 
ODBC-compliant database. The information in the database can be viewed and 
analyzed using WinPM.Net software applications such as Vista (for viewing), or 
Reporter (for organizing and presenting data). 
Data Logging (9330 and 9350)
The standard configuration of the meter includes data recorders that log various 
power system data such as energy and demand, or the average power system 
quantity used over a period of time (Historic Mean Log). The 9350 also logs sags 
and swells in voltage. 
Reporting
The Data Recorder module labeled E
GY
 D
MD
 L
OG
 is configured to provide power 
system data for Reporter software to create reports from the device’s logs. If any 
input links to this module are changed, Reporter will not be able to create reports. 
If you use the Reporter software, do not change the parameters that are logged in 
the Egy Dmd Log. 
Revenue Logging
For the revenue meter option, Data Recorder #1 is locked, so channels must be 
specified prior to the meter being sealed. Refer to RMICAN Ordering Sheet on our 
website for your particular meter.
N
OTE
For compatibility with the UTS MV-90 billing software, Data Recorder #1 must be configured as a 16-
channel recorder. 
To learn more about the data recorder modules in your meter, refer to ION Device 
Templates
 at www.sea.siemens.com. ION Device Templates located at 
www.sea.siemens.com lists all of the ION modules available in the current version 
of your meter, and the total number of each module. ION Device Templates also 
shows the ranges or options available for each module’s setup registers.
Changing Parameters that are Logged
The factory-configured meter logs a comprehensive set of parameters. Adding or 
deleting log parameters is an advanced procedure that requires changing links 
between modules using Designer software.
Once you are comfortable editing module links, change logged parameters by 
linking the output registers you want logged to the inputs of an ION Data 
Recorder module.