9300 Series User’s Guide
Event Logging
Chapter 5 - Features and Applications 
Page 127
Event Logging
Events produced by the various ION modules in the meter are prioritized and 
grouped to facilitate custom logging. Each event has a priority group number 
assigned to it, based on its type and severity. 
ION Event Priority Groups
Some event groups are preset with a Priority Number as shown in the table below. 
You can also define your own priority number for some modules. Priority 
numbers from 128-191 appear in the global even log viewer in WinPM.Net 
software. Priority numbers from 192-255 are logged, initiate a beep and cause the 
window to flash. You can customize these responses to display messages or 
perform netsend messages, for example.
The Event Log Controller module allows you to set a priority cutoff for event 
logging. Any events with a priority number greater than the cutoff value are 
logged, and events with lower priorities are discarded. Refer to the individual 
module descriptions and the Event Log Controller module description in the 
online ION Programmer’s Reference for more details. 
External ION Events
Some events are not produced by a specific module; they are generated internally 
by the meter. These events and their associated priority levels are as follows:.
Event Group
Description
Priority 
Number
Reset
Module reset or resynchronized
5
Setup Change
Module setup changes 
10
Input Register Change
Inputs of certain modules change value
15
I/O State Change
I/O state changes (i.e. relay closes)
20
Information
Module produces important user information
25
Warning
Module produces a warning
30
Failure
A failure has occurred
255
Event Group
Description
Priority 
Number
Warning
Factory initialize performed
30
Firmware upgrade performed
Memory upgrade performed
Device power-up
Device power-down
Failure
Communications fail to allocate required memory
255