9300 Series User’s Guide
Time Synchronization
Chapter 5 - Features and Applications 
Page 129
Time Synchronization
Time synchronization lets you synchronize the internal clocks of all networked 
meters and devices. Once synchronized, all data logs have timestamps that are 
relative to a uniform time base. This allows you to achieve precise sequence-of-
events and power quality analyses. To synchronize clocks, use ACCESS software 
to broadcast time signals across the network.
Refer to the technical note Time Synchronization and Timekeeping for more 
information on implementing time synchronization for your system.
Enabling or Customizing Time Synchronization
1.
Launch the Management Console.
2.
From the System Setup Pane, select Sites or Devices.
Select Sites if you want to customize a particular serial, modem, or Ethernet 
Gateway site.
Select Devices if you want to customize an individual Ethernet device.
3.
Right-click in the main window and select Properties.
4.
Right-click inside the display window and select Advanced Properties.
The fields for enabling or customizing time synchronization are shown below.
The Property Description area explains the purpose for each field. The default time 
synchronization interval of 3,600 seconds (displayed in milliseconds) is acceptable 
for most ION installations.
N
OTE
You need appropriate permissions to configure the meters on your network. Refer to the technical note
ION Security 
for details on software and meter security.
These fields appear in 
the Devices Advanced 
Properties screen for 
Ethernet devices. Serial 
devices are configured 
via the Serial Site
advanced properties.
Use these fields on the Site Advanced 
Properties screen to enable time
synchronization or set custom 
intervals for any device in any Serial 
Site or Ethernet Gateway Site.