Справочник Пользователя для Hitachi SJ300-037HFE

Скачать
Страница из 289
SJ300 Inverter
Configur
ing Dr
iv
P
a
ra
met
e
rs
3–69
NOTE: Set frequency (speed) values are not permitted to be inside the jump frequency ranges, 
if defined. When a frequency reference value from a real-time source (such as keypad potenti-
ometer or analog input) are inside a jump frequency range, the actual speed is automatically 
forced to equal the lowest point of the jump range.
Programming Error 
Code
Parameter out of bounds
Boundary defined by...
Code
Description
<, >
Code
Description
091 291
A061 / A261
Frequency upper limit 
setting; 1st, 2nd motor
>
B112
Free-setting V/f frequency (7)
092 292
A062 / A262
Frequency lower limit 
setting; 1st, 2nd motor
>
095 295
F001,
A020 / A220
Output frequency setting, 
Multi-speed freq. setting; 
1st, 2nd motor
>
096
A021 to A035 Multi-speed freq. settings
>
110
B100, B102, 
B104, B106, 
B108, B110
Free V/f frequency
>
B102, B104, 
B106, B108, 
B110
Free V/f frequency
>
B100
Free-setting V/f frequency (1)
B100
Free V/f frequency
<
B102
Free-setting V/f frequency (2)
B104, B106, 
B108, B110
Free V/f frequency
>
B100, B102
Free V/f frequency
<
B104
Free-setting V/f frequency (3)
B106, B108, 
B110
Free V/f frequency
>
B100, B102, 
B104
Free V/f frequency
<
B106
Free-setting V/f frequency (4)
B108, B110
Free V/f frequency
>
B100, B102, 
B104, B106
Free V/f frequency
<
B108
Free-setting V/f frequency (5)
B110
Free V/f frequency
>
B100, B102, 
B104, B106, 
B108
Free V/f frequency
<
B110
Free-setting V/f frequency (6)
120
B017, B019
Free-setting electronic 
thermal frequency
<
B015
Free-setting, electronic 
thermal frequency (1)
B015
Free-setting electronic 
thermal frequency
>
B017
Free-setting, electronic 
thermal frequency (2)
B019
Free-setting electronic 
thermal frequency
<
B015, B017
Free-setting electronic 
thermal frequency
>
B019
Free-setting, electronic 
thermal frequency (3)