4–21
External Trip
When the terminal [EXT] is turned ON, the inverter enters the trip state, indicates error code 
E12, and stops the output. This is a general purpose interrupt type feature, and the meaning of 
the error depends on what you connect to the [EXT] terminal. Even if [EXT] is turned OFF, the 
inverter remains in the trip state. You must reset the inverter or cycle power to clear the error, 
returning the inverter to the Stop Mode.
In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter 
lets the motor free-run to a stop, and the alarm output turns ON immediately. When the 
operator initiates a Reset command, the alarm and error are cleared. When the Reset is turned 
OFF, the motor begins rotation since the Run command is already active. 
Opt.
Code
Symbol
Function Name
Input 
State
Description
12
EXT
External Trip
ON
When assigned input transitions OFF to 
ON, inverter latches trip event and 
displays E12
OFF
No trip event for ON to OFF, any recorded 
trip events remain in history until Reset
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
(none)
Notes: 
• 
If the USP (Unattended Start Protection) 
feature is in use, the inverter will not automat-
ically restart after cancelling the EXT trip 
event. In that case, it must receive either 
another Run command (OFF-to-ON transi-
tion), a keypad Reset command, or an [RS] 
intelligent terminal input signal.
[EXT]
 [FW, RV]
[RS]
Motor revolution speed
Alarm output terminal
t
 free run
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
.
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
EXT