MDS-D-SVJ3/SPJ3 Series Specifications Manual
6-1 Selection of wire
(3) 600V bridge polyethylene insulated wire (IC) 105 °C product 
(Example according to JEAC8001)
                            Terminal name
Unit type
CNP1
(L1, L2, L3, 
)
CNP2
(L11, L21)
CNP3
(U, V, W, 
)
CNP2
(P,C)
Magnetic
brake
mm
2
AWG
mm
2
AWG
mm
2
AWG
mm
2
AWG
mm
2
AWG
Spindle
drive 
unit
MDS-D-SPJ3-075NA
2
14
1.25
16
2
14
2
14
---
---
MDS-D-SPJ3-22NA
2
14
2
14
MDS-D-SPJ3-37NA
2
14
2
14
MDS-D-SPJ3-55NA
2
14
3.5
12
MDS-D-SPJ3-75NA
3.5
12
3.5
10
3.5
12
MDS-D-SPJ3-110NA
5.5
10
5.5
10
Servo
drive 
unit
MDS-D-SVJ3-03NA
2
14
1.25
16
2
14
2
14
1.25
16
MDS-D-SVJ3-04NA
2
14
2
14
MDS-D-SVJ3-07NA
2
14
2
14
MDS-D-SVJ3-10NA
2
14
2
14
MDS-D-SVJ3-20NA
2
14
2
14
MDS-D-SVJ3-35NA
2
14
3.5
12
1. Selection conditions follow IEC/EN60204-1, UL508C, JEAC8001.
    - Ambient temperature is maximum 40°C.
    - Cable installed on walls without ducts or conduits.
    To use the wire under conditions other than above, check the standards you are supposed to 
follow.
2. The maximum wiring length to the motor is 30m.
If the wiring distance between the drive unit and motor is 20m or longer, use a thick wire so that the 
cable voltage drop is 2% or less.
3. Always wire the grounding wire.
CAUTION