6 Specifications of Peripheral Devices
MITSUBISHI CNC
6-2 Selection of circuit protector and contactor
Always select the circuit protector and contactor properly, and install them to each drive unit to prevent disasters.
6-2-1 Selection of circuit protector
Calculate a circuit protector selection current from the rated output and the nominal input voltage of the drive unit 
as in the expression below. And then select the minimum capacity circuit protector whose rated current meets the 
circuit protector selection current.
Circuit protector selection current [A] = 
(Circuit protector selection current for 200V input [A] / Nominal input voltage [V]) × 200 [V]
Selection of circuit protector for 200V input
Option part: A circuit protector is not prepared as an NC unit accessory, so purchase the part from your 
dealer, etc.
Unit type
MDS-D-SVJ3-
03NA
04NA
07NA
10NA
20NA
35NA
Rated output
0.3kW
0.4kW
0.75kW
1.0kW
2.0kW
3.5kW
Circuit protector selection 
current for 200V input
2.5A
5A
7A
8A
10A
15A
Selection example of circuit protector
(Mitsubishi Electric Corp.)
NF30-
SW3P-5A
NF30-
SW3P-10A
NF30-
SW3P-15A
NF30-
SW3P-15A
NF30-
SW3P-20A
NF30-
SW3P-30A
Rated current of the selection example of 
circuit protector
5A
10A
15A
15A
20A
30A
Unit type
MDS-D-SPJ3-
075NA
22NA
37NA
55NA
75NA
110NA
Rated output
0.75kW
2.2kW
3.7kW
5.5kW
7.5kW
11kW
Circuit protector selection current for 
200V input
6A
9A
15A
23A
31A
45A
Selection example of circuit protector
(Mitsubishi Electric Corp.)
NF30-
SW3P-15A
NF30-
SW3P-20A
NF30-
SW3P-30A
NF50-
SW3P-50A
NF100-
SW3P-60A
NF100-
SW3P-
100A
Rated current of the selection example of 
circuit protector
15A
20A
30A
50A
60A
100A
1. It is dangerous to share a circuit protector for multiple drive units, so do not share it. Always install 
the circuit protectors for each drive unit.
2. If the control power (L11, L21) must be protected, select according to the section "6-4-1 Circuit 
protector ".
CAUTION