6. Installation 
 
 
 
 
 
6 - 11
6-2-6  Heat radiation countermeasures 
 
(1)  Heat radiation countermeasures in the control panel
 
In order to secure reliability and life, design the temperature in the panel so that the ambient 
temperature of each unit is 55°C or less. 
If the heat accumulates at the top of the unit, etc.,
 
install a fan or heat exchanger so that the 
temperature in the panel remains constant.
 
 
 
Please refer to following method for heat radiation countermeasures. 
 
 
<Point> 
[1] Refer to the section “6-5 Heating value” for the heat 
generated by each unit. 
[2] Refer to the following calculation for calculation W1 of the 
panel’s cooling capacity (thin steel plate). 
W1 = U x A x  ΔT 
U: 6W/m
2
 x °C    (with internal agitating fan) 
4W/m
2
 x °C    (without internal agitating fan) 
A: Effective heat radiation area [m
2
(Heat dissipation area in panel) 
Sections contacting other objects are excluded. 
T: Internal temperature rise value (10°C) 
[3] Points in manufacturing and evaluation 
Understanding the temperature rise in the panel, and 
install a fan or heat exchanger. 
T (average value) 10°C 
T
max
 (maximum value) 
15°C 
<Hypothetical conditions> 
[1] Average temperature in panel: T 
55°C 
[2] Panel peripheral temperature: Ta 
0 to 45°C 
[3] Internal temperature rise value: 
T=T-Ta
max 
=10°C 
Calculate total heat radiation of each
unit in panel (W) 
Manufacturing and evaluation 

W1 
W>W1 
ΔT > 10℃ 
ΔT 

10℃ 
Completion 
Evaluate temperature 
in panel 
Comparison of   
W and W1 
Calculate panel’s cooling capacity 
(W1)
 
Consider heat 
exchanger 
Consider adding fan or 
heat exchanger 
 
 
 
Examples of mounting heat exchanger and temperature measurement positions (reference) 
 
 
Temperature measurement positions 
He
a
ex
c
han
g
er
 
Heat 
exchanger
Unit 
Relay, etc 
Unit
 
Flow of air 
Flow of air
Relay, etc