6. Installation 
 
 
 
 
 
6 - 12
 
The following shows a calculation example for considering heat radiation countermeasures. 
 
<Control panel outline dimension (assumption) > 
When installing four units which have the heating value in the panel of 15W 
Top of panel inside      Fan for agitating
600 
300
600
 
 
 
Heat radiation area (A): When a bottom section contacts with a machine 
A = 0.6 x 0.3 + 0.6 x 0.6 x 2 + 0.6 x 0.3 x 2 = 1.26 (m
2
 
(Top face)  (Front/back face)   (Side face) 
*Actually, sections contacting other objects are excluded.  
 
Heating value in panel (W): when installing four units which are 15W
 
W = 15 x 4 = 60 (W) 
 
<Considering nec
essity of agitating f
an> 
1 Temperature standard 
(1) Standard of temperature in panel (around each unit)
   
 55°C
 
(2) External peripheral temperature
               
                     Ta = 0 to 45°C  
(3) Internal temperature rise value                                    
T = T - Ta(MAX) = 10°C 
 
2 C
ooling 
capacity of control panel (W1) 
W1 = U x A x 
T                   T = Internal temperature rise value (=10°C) 
U = 6W/m
2
 
 °C (with internal agitating fan) 
4W/m
2
 
 °C (without internal agitating fan) 
A = Effective heat radiation area (m
2
 
(1) With internal agitating fan      W1 = 6 x 1.26 x 10 = 75.6 (W) > 60 (W) 
Internal fan is  
required. 
(2) Without internal agitating fan  W1 = 4 x 1.26 x 10 = 50.4 (W) < 60 (W) 
 
 
 
 
POINT
 
Measure an actual internal temperature, and install a fan or heat exchanger 
which agitates the heat at the top of the unit if the temperature rise exceeds 
10°C.