9. Adjustment 
 
 
 
 
 
9 - 3
9-1-3  Setting the output magnification 
 
Set as follows to output with a unit other than the standard output unit. 
(Example 1)  When SV061 = 11 and SV063 = 2560 
The position droop is output as a 0.1mm/V unit to D/A output channel 1. 
(Example 2)  When SV062 = 11 and SV064 = 128 
The position droop is output as a 2mm/V unit to D/A output channel 2. 
 
No. 
Abbrev. 
Parameter name 
Explanation 
Setting range
SV063  DA1MPY  D/A output channel 1 output 
magnification 
SV064  DA2MPY  D/A output channel 2 output 
magnification 
When "0" is set, the data is output with the standard output unit. 
Set a value other than 0 to change the output unit. 
The scale is set with a 1/256 unit. When 256 is set, the unit is the 
same as the standard output unit. 
-32768 to 32767
 
9-1-4  Current feedback analog output function 
 
Use this function to measure the resonance frequency when adjusting machine resonance suppression 
filter. 
 
20 ms 
Current feedback: 9 crests
9 cycles
20 x 10
-3
 s
= 450 Hz
Machine 
resonance 
frequency 
Set the speed loop gain (SV005: VGN1) to approx. 50 to 100, disconnect the 
resonance filter, and measure the waveform while the axis is stopped. 
The phase current is output to the CN9 
pin. Connect a high-speed waveform 
recorder, etc. between the GND (pin 1) 
and the phase current to be measured, 
and observe the state. 
6: L axis U-phase current FB 
16: L axis V-phase current FB 
7: M axis U-phase current FB