Справочник Пользователя для Mitsubishi Electronics MDS-R

Скачать
Страница из 362
 
9. Adjustment 
 
 
 
 
 
9 - 6
(2)  Setting the speed loop leading compensation 
The speed loop leading compensation (SV008 (VIA)) determines the characteristics of the speed 
loop mainly at low frequency regions. 1364 is set as a standard, and 1900 is set as a standard 
during SHG control. The standard value may drop in respect to loads with a large inertia.  
When the VGN1 is set lower than the standard value because the load inertia is large or because 
machine resonance occurred, the speed loop control band is lowered. If the standard value is set in 
the leading compensation in this status, the leading compensation control itself will induce vibration. 
In concrete terms, a vibration of 10 to 20Hz could be caused during acceleration/deceleration or 
stopping, and the position droop waveform could be disturbed when accelerating to a constant 
speed and when stopped. (Refer to the following graphs.) 
This vibration cannot be suppressed by the vibration suppression functions. Lower the VIA in 
increments of 100 from the standard setting value. Set a value where vibration does not occur and the 
position droop waveform converges smoothly. Because lowering the VIA causes a drop in the position 
control's trackability, the vibration suppression is improved even when a disturbance observer is used 
without lowering the VIA. (Be careful of machine resonance occurrence at this time.) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
If VIA is lowered, the position droop waveform becomes smooth and overshooting does not occur. 
However, because the trackability in respect to the position commands becomes worse, the 
positioning time and accuracy are sacrificed. VIA must be kept high (set the standard value) to 
guarantee precision, especially in high-speed contour cutting (generally F = 1000 or higher). For 
machines which aim to attain a high speed and high accuracy, set VGN1 to a sufficiently large value 
so that VIA does not need to be lowered. When adjusting, the cutting precision will be better if 
adjustment is carried out to a degree where overshooting does not occur and a high VIA is maintained, 
without pursuing position droop smoothness.  
If there are no vibration or overshooting problems, the high-speed contour cutting precision can be 
further improved by setting the VIA higher than the standard value. In this case, adjust by raising 
the VIA in increments of 100 from the standard value. 
Setting a higher VIA improves the trackability regarding position commands in machines for which 
cycle time is important, and the time to when the position droop converges on the in-position width 
is shortened.  
It is easier to adjust the VIA to improve precision and cycle time if a large value (a value near the 
standard value) can be set in VGN1, or if VGN1 can be raised equivalently using the disturbance 
observer.  
 
No. 
Abbrev. 
Parameter name 
Explanation 
Setting range
SV008 
VIA 
Speed loop lead 
compensation 
Set the gain of the speed loop integration control. 
The standard setting is "1364". During the SHG control, the standard 
setting is "1900". Adjust the value by increasing/decreasing it by about 
100 at a time. 
Raise this value to improve contour tracking precision in high-speed 
cutting. Lower this value when the position droop vibrates (10 to 20Hz). 
1 to 9999 
 
 
 
POINT
 
Position droop vibration of 10Hz or less is not leading compensation control 
vibration. The position loop gain must be adjusted. 
 
Vibration waveform with leading compensation control
Adjusted position droop waveform
Speed FB 
0
T me
i
0
D/A output range
Time
Time
Time
Position 
droop