7.  Diagnosis 
7.4  PLC Interface Diagnosis 
 
 
 
I-289 
 
(2)  Cancel of forcibly defined data 
 
Set two slashes // in DEVICE 
(   ). 
Press the 
 
 
INPUT 
 key. 
ALARM SERVO SPINDLE 
PLC-I/F 
MENU 
  DEVICE  DATA 
MODE  DEVICE  DATA  MODE
    (    //    )    (          )      (    ) 
(            )    (          )      (    ) 
The <SET DATA> field display becomes all blank 
and forcibly defined data is canceled. 
(Setting of data 0 is not a cancel. 
Data of 0 is forcibly defined.) 
 
 
Forcibly defined data is also canceled by turning ON/OFF power. 
 
 
7.4.5  Diagnosis Executed When an Emergency Stop Status Occurs 
 
 
When the NC is put in an emergency stop status, the message "EMG" (emergency stop) is displayed in the 
running status display area of the setting and display unit. At this time, the cause can be known. 
 
(1)  Check using the DIAGN screen 
 
Set R69 in the DEVICE (        ) and 
then press 
 
 
INPUT 
 key. 
  DEVICE      DATA      MODE 
  ( R69 )        (          )      (        ) 
[PLC-I/F] 
 
7  6  5  4  3  2  1  0  HEX 
R0069 
1  1  1  1  1  1  1  1  FF 
 
1  1  1  1  1  1  1  1  FF 
 
Bit 
9
4
3
2
1
0
State  
1
1
1
1
1
1
 
R0069 
(0: EMG stop   1: Normal) 
Built-in PLC  Stop state 
Control unit EMG connector    Emergency stop state 
Built-in PLC    Software emergency stop output device Y29F is "1".
Servo amplifier emergency stop output 
Spindle amplifier emergency stop output 
Door interlock, dog/OT arbitrary allocation device illegal 
External PLC    FROM, TO command not executed 
External PLC  Not ready 
User PLC    Illegal codes exist. 
PLC high-speed processing error 
External PLC  Renewal error