7.  Diagnosis 
7.6  Adjustment 
 
 
 
I-294 
7.6.3  Adjustment Procedure 
 
 
1)  Offset adjustment (Ex. ch0) 
  
(1) 
Select 
#101. 
 
 
 
→ "ch0 offset" will be highlighted, indicating that it is being adjusted. 
 
 
 
The current setting value will display in the "TEMP.DATA" column. 
 
 
(2) Monitor the analog output voltage. 
 
 
(3) Adjust the monitor voltage to 0V 
± 3.5mV. (Setting range: −999~999) 
 
 
 
For a positive voltage, press the 
 
 
 
 key. The adjustment value will decrement in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
 
 
 
For a negative voltage, press the 
 
 
 
 key. The adjustment value will increment in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
  
(4) 
Press 
 
 
INPUT 
 after completing the adjustment. 
 
 
 
→ The TEMP DATA will be saved as the setting value and the adjustment will be validated. 
 
 
 
The "ch0 offset" display will return to the normal display. 
 
2)  +gain adjustment (Ex. ch0) 
  
(1) 
Select 
#102. 
 
 
 
→ "+gain" will be highlighted, indicating that it is being adjusted. 
 
 
(2) The current setting value will display in the "TEMP.DATA" column. 
 
 
(3) Monitor the analog output voltage. 
 
 
 
Adjust the monitor voltage to 10V 
± 3.5mV. (Setting range: −999~999) 
 
 
 
For 10V or more, press the 
 
 
 
 key. The adjustment value will decrement in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
 
 
 
For 10V or less, press the 
 
 
 
 key. The adjustment value will increment in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
  
(4) 
Press 
 
 
INPUT 
 after completing the adjustment. 
 
 
 
→ The TEMP DATA will be saved as the setting value and the adjustment will be validated. 
 
 
 
The "+gain" display will return to the normal display. 
 3) 
−gain adjustment (Ex. ch0) 
  
(1) 
Select 
#103. 
 
 
 
→ "−gain" will be highlighted, indicating that it is being adjusted. 
 
 
 
The current setting value will display in the "TEMP.DATA" column. 
 
 
(2) Monitor the analog output voltage. 
 
 
(3) Adjust the monitor voltage to 
−10V ± 3.5mV. (Setting range: −999~999) 
  
 
For 
−10V or more, press the 
 
 
 
 key. The adjustment value will decrement in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
  
 
For 
−10V or less, press the 
 
 
 
 key. The adjustment value will increment in units of 100 when 
 
 
SHIFT 
 
 
 
 
 are pressed. 
  
(4) 
Press 
 
 
INPUT 
 after completing the adjustment. 
 
 
 
→ The TEMP DATA will be saved as the setting value and the adjustment will be validated. 
  
 
The 
"
−gain" display will return to the normal display.