DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-573
test duplication-interface 
8
test duplication-interface
This command will test the indicated duplication-interface board.
Synopsis
test duplication-interface location 
[ short | long ][ repeat number | clear ] 
schedule
Permissions
The following default logins may execute this command: system technician, 
inads, init.
Examples
test duplication-interface a
test duplication-interface b sh
test duplication-interface a l r 25
test duplication-interface 1b l r 25 schedule
test duplication-interface 1a l c
Description
The test duplication-interface command performs hardware diagnostic tests on 
the indicated duplication interface circuit pack. Testing is under control of the 
active SPE. The SHDW-CIR, SPE-SELECT and DUPINT maintenance objects are 
tested using this command. The SHDW-CIR maintenance object is associated 
with that portion of the duplication interface circuit pack that handles memory 
shadowing from the active to the standby SPE. The SPE-SELECT maintenance 
objects is associated with the SPE Select switch located on the front of the circuit 
pack. The DUPINT maintenance object is associated with the duplication 
interface circuit packs other functions which include SPE to SPE communication, 
SAT connection and environmental maintenance leads.
Defaults
Defaults for the parameters are short with a repeat of 1.