11 - 44 11 - 44
MELSEC-Q
11 TROUBLESHOOTING
Special Relay List
(2) System information
Number
Name
Meaning
Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Applicable
CPU
SM202
LED OFF
command
command
OFF
ON : LED OFF
• When this relay goes from OFF to ON, the LEDs
corresponding to the individual bits at SD202 go off
U New
SM203 STOP contact
STOP status
• Goes ON at STOP status
S (Status
change)
M9042
SM204 PAUSE contact
PAUSE status
• Goes ON at PAUSE status
S (Status
change)
M9041
SM205
STEP-RUN
contact
contact
STEP-RUN status
• Goes ON at STEP-RUN status
S (Status
change)
M9054
PAUSE enable
coil
coil
OFF : PAUSE disabled
ON : PAUSE enabled
ON : PAUSE enabled
• PAUSE status is entered if this relay is ON when the
remote PAUSE contact goes ON
U M9040
SM206
Device test
request
acceptance
status
request
acceptance
status
OFF : Device test not yet
executed
ON : Device test executed
• Comes ON when the device test mode is executed on
GX Developer.
S (Request)
New
Remote
SM210
Clock data set
request
request
OFF : Ignored
ON : Set request
ON : Set request
• When this relay goes from OFF to ON, clock data being
stored from SD210 to SD213 after execution of END
instruction for changed scan is written to the clock device.
instruction for changed scan is written to the clock device.
U M9025
SM211 Clock data error
OFF : No error
ON : Error
ON : Error
• ON when error is generated in clock data (SD210 to
SD213) value, and OFF if no error is detected.
S (Request)
M9026
SM212
Clock data
display
display
OFF : Ignored
ON : Display
ON : Display
• Displays clock data as month, day, hour, minute, and
second at the LED display at front of CPU module.
U M9027
Q3A
Q4A
Q4A
Q4AR
SM213
Clock data read
request
request
OFF : Ignored
ON : Read request
ON : Read request
• When this relay is ON, clock data is read to SD210 to
SD213 as BCD values.
U M9028
+Rem
SM240
No. 1 CPU reset
flag
flag
OFF : PLC No. 1 reset cancel
ON : PLC No. 1 resetting
ON : PLC No. 1 resetting
• Goes OFF when reset of the PLC No. 1 is canceled.
• Comes ON when the PLC No. 1 is resetting (including
• Comes ON when the PLC No. 1 is resetting (including
the case where the PLC is removed from the base unit).
The other PLCs are also put in reset status.
The other PLCs are also put in reset status.
SM241
No. 2 CPU reset
flag
flag
OFF : PLC No. 2 reset cancel
ON : PLC No. 2 resetting
ON : PLC No. 2 resetting
• Goes OFF when reset of the PLC No. 2 is canceled.
• Comes ON when the PLC No. 2 is resetting (including
• Comes ON when the PLC No. 2 is resetting (including
the case where the PLC is removed from the base unit).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
SM242
No. 3 CPU reset
flag
flag
OFF : PLC No. 3 reset cancel
ON : PLC No. 3 resetting
ON : PLC No. 3 resetting
• Goes OFF when reset of the PLC No. 3 is canceled.
• Comes ON when the PLC No. 3 is resetting (including
• Comes ON when the PLC No. 3 is resetting (including
the case where the PLC is removed from the base unit).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
SM243
No. 4 CPU reset
flag
flag
OFF : PLC No. 4 reset cancel
ON : PLC No. 4 resetting
ON : PLC No. 4 resetting
• Goes OFF when reset of the PLC No. 4 is canceled.
• Comes ON when the PLC No. 4 is resetting (including
• Comes ON when the PLC No. 4 is resetting (including
the case where the PLC is removed from the base unit).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
The other PLCs result in "MULTI CPU DOWN" (error
code: 7000).
SM244
No. 1 CPU error
flag
flag
OFF : PLC No. 1 normal
ON : PLC No. 1 during stop
ON : PLC No. 1 during stop
error
• Goes OFF when the PLC No. 1 is normal (including a
continuation error).
• Comes ON when the PLC No. 1 is during a stop error.
SM245
No. 2 CPU error
flag
flag
OFF : PLC No. 2 normal
ON : PLC No. 2 during stop
ON : PLC No. 2 during stop
error
• Goes OFF when the PLC No. 2 is normal (including a
continuation error).
• Comes ON when the PLC No. 2 is during a stop error.
SM246
No. 3 CPU error
flag
flag
OFF : PLC No. 3 normal
ON : PLC No. 3 during stop
ON : PLC No. 3 during stop
error
• Goes OFF when the PLC No. 3 is normal (including a
continuation error).
• Comes ON when the PLC No. 3 is during a stop error.
SM247
No. 4 CPU error
flag
flag
OFF : PLC No. 4 normal
ON : PLC No. 4 during stop
ON : PLC No. 4 during stop
error
• Goes OFF when the PLC No. 4 is normal (including a
continuation error).
• Comes ON when the PLC No. 4 is during a stop error.
S (Status
change)
New
QCPU
function
Ver. B