[DESIGN PRECAUTIONS] 
!
 DANGER 
 When overcurrent which exceeds the rating or caused by short-circuited load flows in the output 
module for a long time, it may cause smoke or fire. To prevent this, configure an external safety 
circuit, such as fuse. 
 
 Build a circuit that turns on the external power supply when the PLC main module power is 
turned on. If the external power supply is turned on first, it could result in erroneous output or 
erroneous operation. 
 
 When there are communication problems with the data link, refer to the corresponding data link 
manual for the operating status of each station. Not doing so could result in erroneous output or 
erroneous operation. 
 
 When connecting a peripheral device to the CPU module or connecting a personal computer or 
the like to the intelligent function module to exercise control (data change) on the running PLC, 
configure up an interlock circuit in the sequence program to ensure that the whole system will 
always operate safely. 
Also before exercising other control (program change, operating status change (status control)) 
on the running PLC, read the manual carefully and fully confirm safety. 
Especially for the above control on the remote PLC from an external device, an immediate 
action may not be taken for PLC trouble due to a data communication fault. 
In addition to configuring up the interlock circuit in the sequence program, corrective and other 
actions to be taken as a system for the occurrence of a data communication fault should be 
predetermined between the external device and PLC CPU. 
 
!
 CAUTION 
 Do not bunch the control wires or communication cables with the main circuit or power wires, or 
install them close to each other. They should be installed 100 mm (3.94 inch) or more from 
each other. Not doing so could result in noise that would cause erroneous operation. 
 
 When controlling items like lamp load, heater or solenoid valve using an output module, large 
current (approximately ten times greater than that present in normal circumstances) may flow 
when the output is turned OFF to ON. 
Take measures such as replacing the module with one having sufficient rated current.