6 - 1                                                                                                                                                       6 - 1 
MELSEC-Q
 
6   BASE UNIT AND EXTENSION CABLE 
 
6 BASE UNIT AND EXTENSION CABLE 
This section describes the specifications of the extension cables for the 
base units (main, slim type and extension base unit) used in the PLC 
system and the specification standards of the extension base unit. 
 
6.1 Base Unit Specification Table 
(1) Main base unit specifications 
 
Type 
Item 
Q33B Q35B Q38B Q312B 
Number of I/O modules 
installed 
3 5 8 12 
Possibility of extension 
Extendable 
Applicable module 
Q series modules 
5 VDC internal current 
consumption 
0.105A 0.110A 0.114A 
 0.121A 
Mounting hole size 
M4 screw hole or  4.5 hole (for M4 screw) 
H 98mm 
(3.86inch) 
189mm (7.44inch) 
245mm (9.65inch) 
328mm (12.92inch) 
439mm (17.30inch) 
External 
dimensions 
D 44.1mm 
(1.74inch) 
Weight 
0.21kg 
0.25 kg 
0.35 kg 
0.45 kg 
Attachment 
Mounting screw M4 14 4 pieces (DIN rail mounting adapter to be sold separately) 
DIN rail mounting 
Adapter type 
Q6DIN3 Q6DIN2 
Q6DIN1 
 
(2) Slim type main base unit specifications 
 
Type 
Item 
Q32SB Q33SB Q35SB 
Number of I/O modules 
installed 
2 3 5 
Possibility of extension 
Cannot connect extension modules. 
Applicable module 
Q series modules 
5 VDC internal current 
consumption 
0.086A 0.086A 0.091A 
Mounting hole size 
M4 screw hole or  4.5 hole (for M4 screw) 
H 98mm 
(3.86inch) 
114mm (4.49inch) 
142mm (5.59inch) 
198mm (7.80inch) 
External 
dimensions 
D 18.5mm 
(0.73inch) 
Weight 
0.12kg 
0.15 kg 
0.21 kg 
Attachment 
Mounting screw M4 12 4 pieces (DIN rail mounting adapter to be sold separately) 
DIN rail mounting 
Adapter type 
Q6DIN3