Справочник Пользователя для Mitsubishi Electronics Q25HCPU

Скачать
Страница из 236
 
 
 
6 - 9                                                                                                                                                       6 - 9 
MELSEC-Q
 
6   BASE UNIT AND EXTENSION CABLE 
 
List for Calculating Voltage Drops Occurring at Extension Cables in System Consisting of Extensions 1 to 7 
 
Voltage Drop at Extension Cable on Corresponding Extension Unit 
Q5
†B 
Loading 
Position 
V1 V2 V3 V4 V5 V6 V7 
Sum Total of Voltage 
Drops to "IN" Connector 
of Q5
†B (V) 
Extension 
stage 1 
R1 
• 
I1 
---- ---- ---- ---- ---- ---- 
V=V1 
Extension 
stage 2 
R1(I1+I2) 
R2 
• 
I2 
---- ---- ---- ---- ---- 
V=V1+V2 
Extension 
stage 3 
R1(I1+I2+I3) 
R2(I2+I3) 
R3 
• 
I3 
---- ---- ---- ---- 
V=V1+V2+V3 
Extension 
stage 4 
R1(I1+I2+I3+I4)  R2(I2+I3+I4) 
R3(I3+I4) 
R4 • I4 
---- 
---- 
---- 
V=V1+V2+V3+V4 
Extension 
stage 5 
R1(I1+I2+I3+I4
+I5) 
R2(I2+I3+I4+I5)  R3(I3+I4+I5) 
R4(I4+I5) 
R5 • I5 
---- 
---- 
V=V1+V2+V3+V4+V5 
Extension 
stage 6 
R1(I1+I2+I3+I4
+I5+I6) 
R2(I2+I3+I4+I5
+I6) 
R3(I3+I4+I5+I6)  R4(I4+I5+I6) 
R5(I5+I6) 
R6 • I6 
---- 
V=V1+V2+V3+V4+V5+
V6 
Extension 
stage 7 
R1(I1+I2+I3+I4
+I5+I6+I7) 
R2(I2+I3+I4+I5
+I6+I7) 
R3(I3+I4+I5+I6
+I7) 
R4(I4+I5+I6+I7)  R5(I5+I6+I7) 
R6(I6+I7) 
R7 • I7 
V=V1+V2+V3+V4+V5+
V6+V7 
 
The voltage supplied to "IN" connector of the Q5
†B in the final extension reaches 4.75 
VDC or higher on the condition that the sum total of voltage drop to "IN" connector of 
Q5
†B (V) is 0.15V or lower. 
 
(2)   When the Q6 B is connected between the Q3 B and the Q5 B 
(a) Selection condition 
4.75VDC or higher should be supplied to the "IN" connector of the Q5
†B in 
the final extension. 
(b) How to calculate voltage to "IN" connector 
The 5VDC output voltage of the power supply module on the main base 
unit is set to at least 4.90VDC. 
Therefore, the Q5
†B can be used if the voltage drop is 0.15VDC or lower 
(4.9VDC - 4.75VDC = 0.15VDC). 
 
Extension Cable 
Type 
Extension Cable 
Conductor 
Resistance ( ) 
QC05B 0.044 
QC06B 0.051 
QC12B 0.082 
QC30B 0.172 
QC50B 0.273 
QC100B 0.530 
[When the Q5   B is connected to Extension stage 2.]
V
R1
I1
Main base unit (Q3   B)
Extension stage 1
Extension stage 2
Power 
supply 
module
Extension base unit (Q6   B) 
Extension base unit (Q5   B) 
Power 
supply 
module
 
 
 
Symbol Description 
Voltage drop at the extension cable between the main base unit and extension base unit (Q5
†
B) 
In 
5VDC current consumption when the Q5
†
B is used as Extension n+1, n = 1 to 6, n: Extension No. of Q6
†
connected 
(Sum total of current consumed by Q5
†
B and currents consumed by the I/O, intelligent function modules 
loaded on the Q5
†
B.) 
Rn 
Extension cable resistance between the main base unit or the extension base unit (Q6
†
B) and the extension 
base unit (Q6
†
B) 
Rn+
1
 
Extension cable resistance between the extension base unit (Q6
†
B) and extension base unit (Q5
†
B)