8   EMC AND LOW VOLTAGE DIRECTIVE 
 
(b)   Positioning modules 
Precautions to be followed when the machinery conforming to the EMC 
Directive is configured using the A1SD75P1-S3/A1SD75P2-S3/A1SD75P3-
S3 (hereafter referred to as the A1SD75) are described below. 
1) When wiring with a 2 m (6.56 ft.) or less cable 
• Ground the shield section of the external wiring cable with the cable 
clamp. (Ground the shield at the closest location to the A1SD75 
external wiring connector.) 
• Wire the external wiring cable to the drive unit and external device with 
the shortest practicable length of cable. 
• Install the drive unit in the same panel. 
P
o
wer suppl
y
m
odul
e
A1
S
D
7
5
m
odul
e
Drive unit
External wiring connector
Cable clamp
External wiring cable (within 2 m (6.56 ft.))
 
2) When wiring with cable that exceeds 2 m (6.56 ft.), but is 10 m (32.79 ft.) 
or less 
• Ground the shield section of the external wiring cable with the cable 
clamp. (Ground the shield at the closest location to the A1SD75 
external wiring connector.) 
• Install a ferrite core. 
• Wire the external wiring cable to the drive unit and external device with 
the shortest practicable length of cable. 
External wiring connector
Ferrite core
External wiring cable (2 m to 10 m (6.56 ft. to 32.79 ft.))
Cable clamp
P
o
wer su
ppl
y
m
odul
e
A1
S
D
7
5
m
odul
e
Drive unit
 
3) Ferrite core and cable clamp types and required quantities 
• Cable clamp 
Type :  AD75CK (Mitsubishi Electric) 
• Ferrite core 
Type :  ZCAT3035-1330 (TDK ferrite core) 
• Required quantity 
 
Required Qty 
Cable length 
Prepared part 
1 axis 
2 axes 
3 axes 
Within 2 m (6.56 ft.) 
AD75CK 
AD75CK  1 1 1 
2 m (6.56 ft.) to 10m 
(32.79ft.) 
ZCAT3035-1330 
1 2 3