Справочник Пользователя для Mitsubishi Electronics Q25HCPU

Скачать
Страница из 236
 
 
 
9 - 9                                                                                                                                                       9 - 9 
MELSEC-Q
 
9   LOADING AND INSTALLATION 
 
9.3 Module Installation 
9.3.1 Precaution on installation 
!
 CAUTION 
 Use the PLC in an environment that meets the general specifications 
contained in this manual. Using this PLC in an environment outside the 
range of the general specifications could result in electric shock, fire, 
erroneous operation, and damage to or deterioration of the product. 
 Hold down the module loading lever at the module bottom, and 
securely insert the module fixing latch into the fixing hole in the base 
unit. Incorrect loading of the module can cause a malfunction, failure or 
drop.When using the PLC in the environment of much vibration, tighten 
the module with a screw. 
Tighten the screw in the specified torque range. Undertightening can 
cause a drop, short circuit or malfunction. Overtightening can cause a 
drop, short circuit or malfunction due to damage to the screw or 
module. 
 When installing more cables, be sure that the base unit and the module 
connectors are installed correctly. After installation, check them for 
looseness. Poor connections could cause an input or output failure. 
 Securely load the memory card by pushing it into the memory card 
loading slot. Check for insecure loading after loading the memory card. 
Not doing so can cause a malfunction due to a contact fault. 
 Completely turn off the external power supply before loading or 
unloading the module. Not doing so could result in electric shock or 
damage to the product. 
 Do not directly touch the module's conductive parts or electronic 
components. Touching the conductive parts could cause an operation 
failure or give damage to the module. 
 
This section gives instructions for handling the CPU, I/O, intelligent function and power 
supply modules, base units and so on. 
 
(1) Module enclosure, terminal block connectors and pin connectors are made of resin; 
do not drop them or subject them to strong impact. 
 
(2) Do not remove modules' printed circuit boards from the enclosure in order to avoid 
changes in operation. 
 
(3) Tighten the module fixing screws and terminal block screws within the tightening 
torque range specified below. 
 
Location of Screw 
Tightening Torque Range 
Module fixing screw (M3   12 screw) 
36 to 48 N 
• 
cm 
I/O module terminal block screw (M3 screw) 
42 to 58 N 
• 
cm 
I/O module terminal block fixing screw (M3.5 screw) 
66 to 89 N 
• 
cm 
Power supply module terminal screw (M3.5 screw) 
66 to 89 N 
• 
cm 
 
(4) Be sure to install the power supply module in the Q3 B, Q6 B and QA1S6 B. 
Even if the power supply module is not installed, when the I/O modules and 
intelligent function module installed on the base units are of light load type, the 
modules may be operated.  In this case, because a voltage becomes unstable, we 
cannot guarantee the operation. 
 
(5) When an extension cable is used, do not bind the cable together with the main 
circuit (high voltage, heavy current) line or lay them close to each other.