® DPoE™ Power Patch Panel User’s Guide 
Issue 2.2 
 
 
Part Number: PN378A 
 
 
 
 
 
  
56
 
 
 
4.  Record the rack space position on the Installation 
Worksheet. 
5. 
Prepare the shielded cables for termination using 
the figures appropriate for the type of cable used. 
Caution: Do not damage conductors
. To ensure 
the highest shielding effectiveness, cut 1.5” (38.1 
mm) of copper tape, included in 4 strips inside the 
Power Patch Panel Installation Kit, and wrap it 
around the cable foil or braid. Refer directly to the 
Installation Instructions or the diagrams below for 
proper cable termination depending on the type of 
shielded cable being used: 
 
 
 
 
 
 
Connecting the Powered Devices 
 
6.  After the cables are properly terminated, place conductors into the punchdown slots in the 
appropriate wiring sequence. In order to support pre-standard powered devices utilizing Cisco 
Inline Power, the ALT POE "A" or ALT POE "B", corresponding to a EIA/TIA 568A or EIA/TIA 
568B configured data pairs, wiring sequence must be used.