5.2  Toshiba ASD (Common Serial) Network in Use 
The gateway connects to each drive via the drive’s common serial (logic level) 
communication port, typically located on either the main drive control board 
(G7, S11), on the front of the drive enclosure under a small snap-on cover (A7, 
S9), on the right-hand side of the drive enclosure under a small snap-on cover 
(S7), or on the bottom side of the drive enclosure (VF-nC1).  Although in 
general no drive parameters need to be configured in order to use the gateway, 
it is advantageous to check that the drive’s common serial communication data 
rate is set to its maximum speed.  Because the gateway will communicate to 
each drive only at the drive’s configured data rate, this will provide the fastest 
response time for drive-to-network data transfers.  For information on checking 
the drive’s common serial communication data rate, refer to the appropriate 
manual supplied with your drive. 
 
Note that the common serial communication parameters of each drive are 
handled independently by the gateway, which means that different drive 
families may be connected to different channels of the unit in any combination, 
and that the drives connected to each channel may simultaneously 
communicate to the unit at completely different baud rates, parity settings, etc. 
 
Drives can be connected to the gateway on any ASD channel in any order or 
combination.  When more than one drive is connected to the unit, or if the 
optional auxiliary power supply is used, the gateway will draw its control power 
from the source with the highest power supply voltage. 
 
Installation of the gateway should only be performed by a qualified technician 
familiar with the maintenance and operation of the connected drives.  To install 
the gateway, complete the steps outlined in the following sections related to 
your specific drive. 
 
 
5.2.1  Installation for G7 ASDs 
1.  Mount the unit via the desired method (refer to page 12 for more 
information). 
2. 
 
CAUTION!
  Verify that all input power sources to the drives to 
be connected have been turned OFF and are locked and tagged out. 
3. 
 
DANGER!
 
 Wait at least 5 minutes for the drive’s 
electrolytic capacitors to discharge before proceeding to the next step.  Do 
not touch any internal parts with power applied to the drive, or for at 
least 5 minutes after power to the drive has been removed.  A hazard 
exists temporarily for electrical shock even if the source power has 
been removed.
  Verify that the CHARGE LED has gone out before 
continuing the installation process.