Справочник Пользователя для Toshiba MBP-100

Скачать
Страница из 73
 
  
17
ICC or your local Toshiba representative for assistance if the problem 
persists. 
 
 
5.2.2  Installation for S7, S9, S11, A7 and VF-nC1 ASDs 
1.  Mount the unit via the desired method (refer to page 12 for more 
information). 
2. 
 
CAUTION!
  Verify that all input power sources to the drives to 
be connected have been turned OFF and are locked and tagged out. 
3. 
 
DANGER!
 
 Wait at least 5 minutes for the drive’s 
electrolytic capacitors to discharge before proceeding to the next step.  Do 
not touch any internal parts with power applied to the drive, or for at 
least 5 minutes after power to the drive has been removed.  A hazard 
exists temporarily for electrical shock even if the source power has 
been removed.
  Verify that the CHARGE LED has gone out before 
continuing the installation process. 
4.  Remove the drive’s common serial communication port cover if it has one 
(refer to the appropriate drive manual for instructions how to do this).  Do 
not discard this cover, as it should be reinstalled to minimize contamination 
of the port’s electrical contacts if the gateway is ever disconnected from the 
drive. 
5.  Connect the drive’s common serial communication port to one of the ASD 
channels of the gateway with the communication cable (communication 
cable is not included with the gateway kit).  When choosing cables for this 
connection, standard 24 AWG category 5 (CAT5) unshielded twisted-pair 
(UTP) 8-conductor cables found in Ethernet networks in most office 
environments can be used.  The maximum allowable length for these 
cables is 5 meters.  Although there are many varieties and styles of CAT5 
UTP cables available, ICC strongly recommends using only high-quality 
cables from reputable manufacturers to guarantee optimal noise immunity 
and cable longevity.  Ensure that each end of the cable is fully seated into 
the modular connectors, and route the cable such that it is located well 
away from any drive input power or motor wiring.  Also take care to route 
the cable away from any sharp edges or positions where it may be 
pinched. 
6.  Repeat steps 2-5 to connect other drive(s) as needed. 
7.  Connect the Modbus Plus network to the “NETWORK” DB9 connector.  Be 
sure to follow all published guidelines pertaining to Modbus Plus network 
connections, layout and routing. 
8.  If an auxiliary power supply is going to be used, connect it to the gateway’s 
“POWER” jack.