Troubleshooting
7 Troubleshooting
7.1
Overview
This chapter describes the procedures used to isolate hardware faults. Three push-
buttons and eight status Led provide verification of TankGate proper operation. If the 
TankGate is not functioning normally, the user is able to troubleshoot the device by 
performing one or more procedures using the three push-buttons. These push-buttons 
and indicators are also described in the Motherboard & I/O Expansion Module 
Configuration chapter. 
7.2
Troubleshooting the TankGate
7.2.1
LED Displays under normal conditions
Operations are normal if the Run, I/O and On-line indicators are flashing. the table below 
represents the normal conditions for the Run, Output and On-line indicators.
TankGate LED Indicators
7.2.1.1
Run indicator
The RUN Indicator provides the single most important feedback of proper system 
operation. When the system functions properly, the RUN Indicator is constantly flashing 
at a 0.5Hz rate. If this indicator ever goes to a steady state condition, either on or off, 
some malfunction has occurred. In addition, relative processor loading can be determined 
Indicator
Condition
Run
Flashes once every second.
Com
Toggles when the system is receiving data. Idle when not receiving 
data.
TXD
Every P011 causes the TXD LED to toggle
RXD
Lights when a response is received