Troubleshooting
TankGate Interface
98 
Installation and Operations Manual
by observing the RUN Indicator duty cycle. Under normal conditions, this indicator 
flashes once every second.
7.2.1.2
Communications indicator
The Communications indicator provides communication line status. When it is toggling, 
the system is exchanging data. As the system receives a valid message from the Host, 
this indicator toggles. If the indicator is idle, the system is off-line.
7.2.1.3
TXD/RXD LEDs
When these LEDs are flashing, the system is exchanging data between the TankGate and 
any tank gauge.
7.2.2
LED Displays under Abnormal Conditions
The table below lists the abnormal conditions of the four indicator lights. From this table 
the user should be able to pinpoint the cause and derive a solution to the problem.
7.2.3
Using the TankGate Push-buttons
7.2.3.1
Reinitializing System Hardware
To reinitialize the system hardware
• 
Press the RESET Switch.
This action causes it to go to a known starting state. This switch may be pressed at any 
time; however, the following will also occur:
• 
Reinitialize System Hardware
• 
Clear Working Memory
• 
Reinitialize Data Base 
Indicator
Condition
Cause
Solution
Run
Does not flash 
(even after hard 
reset)
Bad database
Bad main circuit 
board
Perform Hard Reset then reload 
database
Replace main circuit board
Steady ON/OFF
system failure
Communication
Steady state
DIP switch 
setting
Check unit ID DIP switch 
setting: set ID number and reset 
system
COM point
Check COM point with 
diagnostics terminal or ViewRTU
COM parameters
Verify time-out, baud, and 
protocol parameters have the 
correct values set
bad 
communications
Check for bad communication 
line, modem board or main 
circuit board
wrong jumper 
settings
Check SW1 & SW2 for proper 
settings