Справочник Пользователя для National Instruments SCC-CO20

Скачать
Страница из 15
SCC-CO20 Isolated Current Output Module User Guide
4
ni.com
Figure 1.  SCC-CO20 Signal Connections to E/M Series DAQ Device
Using the Isolated Loop Supply of the SCC-CO20
You can connect the SCC-CO20 to a load using either the isolated internal 
loop supply or an external supply. The internal loop supply outputs a 
voltage of 15 V with respect to the isolated ground reference. When using 
the internal loop supply, the compliance voltage is 12.5 V. This allows for 
a maximum load resistance of 625
Ω at 20 mA. Figure shows how to 
connect the SCC-CO20, using the internal loop supply, to a nonreferenced 
(floating) load and to a load with a high common-mode voltage.
Figure 2.  Connecting the SCC-CO20 Using the Internal Loop Supply
AO GND
E/M Series
DAQ Device
AO ()
SCC-CO20
1
2
+
15 V iso
3
I
High 
CMV
SCC-CO20 
Load 
– 
15 V iso 
0–20 mA 
0–20 mA 
SUPPLY 
SINK 
SCC-CO20 
Load 
– 
15 V iso 
3  SUPPLY 
SINK 
–