When connecting to the condensed water tray, ensure that the condensed water pipe is connected 
to a self-filling siphon with return protection and that the condensed water pipe has a drop. 
The height of the siphon must be designed for an under or overpressure of 800 Pa so that air is 
not drawn in or blown out of the waste pipe.  
 
 
5.5 Electrical 
connection 
 
The wiring diagram is enclosed in the unit. 
 
 
 
 
Make sure the server cabinet is electrically disconnected during  
 
 
installation. Prior to beginning installation work shut down the  
 
 
server cabinet, disconnect it and secure it against unauthorised  
  switch 
on. 
 
 
 
As soon as all preparations for installation have been made, you can start electrical installation. 
 
 
 
 
 
The unit should only be connected by appropriately  
 
 
qualified personnel (electrician). The personnel must ensure  
 
 
that the server cabinet is electrically isolated for the  
 
 
duration of the connection work and is secured against  
  unauthorised 
switch 
on. 
 
 
 
 
Check whether voltage and frequency at installation site as well as 
fuse ratings match the specifications on the rating plate. 
 
Power supply connection is done by a terminal block. 
 
To connect the unit to the power supply: 
• 
Correctly shut down the server cabinet. 
• 
See the wiring diagram for information on the connections to be made. 
• 
Connect the supply cable in the computer room. 
• 
Check the secure connection of the earth wire.  
 
 
 
To put the server cabinet correctly back in operation: 
Switch on the fuse protected power supply. 
The unit's fans will rotate clockwise. 
The status indicator on the RMS viewer will go green if running.