Справочник Пользователя для Gossen R2600

Скачать
Страница из 40
GOSSEN METRAWATT GMBH
23
See 2.4.2.2 for the contents of the function field (FF)
The first character of the data block is the configuration "sensor type". The second character (B marking) cannot be stored, but a character (any, e.g. 
00h) must be sent.
3.6.2
Send a control parameter, for example
The parameter index (PI) is not 3xh, thus the characters "from/to channel" and "receipt No." = 1, 1, 0 are contained in the long set.
Example: Send the Heat proportional band Pb I = 2.3% to R2600/01 with the address = 1 (see 4.2).
Transmission from master (long set, see 2.3):
See 2.4.2.2 for the contents of the function field (FF)
According to 4.2 and 2.4.4, the two characters of the data block (17h, 00h) are calculated to be: Pb I in 0.1% = 23 = 0017h
Acknowledgement from equipment (short set):
10h
00h
„FF“
„FF“
16h
PS
68h
08h
08h
68h
01h
69
10h
01h
01h
00h
17h
00h
93h
16h
FF
PI
PS
Acknowledgement from equipment (short set):
10h
01h
„FF“
„FF“ + 1
16h
PS
Data block