Страница из 40
GOSSEN METRAWATT GMBH
25
03h
Second set point 
± 15 bits
(4.1.2)
SP L ... SP H
04h
High limit for relay A2
± 15 bits
(4.1.2)
Same as PI = 01h
Same as PI = 01h
05h
Low limit for relay A2
± 15 bits
(4.1.2)
Same as PI = 01h
Same as PI = 01h
06h
Low set point
± 15 bits
(4.1.2)
X1 ... SP H
For fixed value controller, 
slave controller
–MBU/2 ... SP H
For differential controller
07h
High set point
± 15 bits
(4.1.2)
SP L ... X2
For fixed value controller, 
slave controller
SP L ... MBU/2
For differential controller
08h
Lower range limit standard signal
± 15 bits
–1500 ... r n H
For B2, B4, B5
09h
Upper limit standard signal
± 15 bits
r n L....9999
For B2, B4, B5
0Ch
Calibration actual value
± 15 bits
(4.1.2)
–MBU/4 ... +MBU/4
For B1, B3, B4 and TC
–MBU/4 = Auto,
–MBU/4 + 1 ... MBU/4
For B1, B3, B4 and Pt100
0Dh Location of decimal point
8 bits
1)
0, 1 = 9.999, 2 = 99.99,
3 = 999.9, 4 = none
For B2, B5
0Eh
Ramp for rising set points
± 15 bits
2)
0 = oFF, 1 ... MBU
0Fh
Ramp for falling set points
± 15 bits
2)
0 = oFF, 1 ... MBU
1) The decimal point is for the display on the R2600/01 only, not for the parameter values.
2) Unit per minute, see 4.1.2 for units