11   MANUAL CONTROL 
 
 Precautions during operation 
 
The following details must be understood before inching operation is carried out. 
(1) Acceleration/deceleration processing is not carried out during inching 
operation. 
(Pulses corresponding to the designated inching movement amount are output 
at the first control cycle of the QD75MH (1.7ms). The movement direction of 
inching operation is reversed and, when a backlash compensation is carried 
out, first pulses corresponding to the backlash amount are output in the first 
control cycle of the QD75MH and then pulses corresponding to the designated 
inching movement amount are output in the subsequent control cycles.) 
The "
Cd.17
JOG speed" is ignored even if it is set. An error will occur in the 
following cases (error code: 301). 
(
Cd.16
Inching movement amount) x (A) > (
Pr.31
JOG speed limit value) 
Where (A) is as follows. 
• When the unit is PLS:  562.5 
• When the unit is degree and the "
 Pr.82
 Speed control 10 x multiplier setting 
for degree axis" is valid:  33.75 
• When the unit is other than the above:  337.5 
 
(2) JOG start signal OFF   ON immediately after stop signal ON   OFF (within 
100 ms) is ignored. 
(Operation will not start.) 
 
(3) Set a value other than a "0" in "
Cd.16
Inching movement amount". 
If a "0" is set, the operation will become JOG operation (Refer to Section 11.2 
"JOG operation"). 
 
 Errors during operation 
 
When the operation is stopped by the stroke limit (limit signal OFF), inching 
operation can be performed out in the direction in which the limit signal turns ON 
after an error reset.  
(JOG start signals in the direction in which the limit signal turns OFF will be 
ignored.) 
 
Inching operation possible
Upper/lower
limit signal
Inching operation
V
Inching operation not possible
ON
OFF