15 - 7 
MELSEC-Q
 
15   TROUBLESHOOTING 
 
 
 
 
 
 
 
Related buffer memory 
address 
 
Axis 1  Axis 2  Axis 3  Axis 4 
Set range  
(Setting with PLC program) 
Remedy 
 
— — — — 
— 
— 
 
 
— — — — 
— 
• Check that there is no influence from noise. 
• Check hardware for possibility of fault. 
 
 
 
 
 
 
 
— — — — 
— 
• Review the PLC program which turns ON/OFF PLC 
READY signal (Y0). 
• Cancel the error with an axis error reset. 
(Refer to Section 15.1[3]) 
 
 
 
— — — — 
— 
Check the servo amplifier power, wiring with the servo 
amplifier, and connection of connectors, and cancel the 
error with an axis error reset. (Refer to Section 15.1[3]) 
 
 
 
 
 
 
 
— — — — 
— 
• Check that there is no error on the personal computer 
side I/F to which a cable is connected. 
• Change the transmission speed (serial communication 
baud rate selection) between the personal computer 
and the QD75MH. (Refer to Section 5.2.9 
Pr.133
 ) 
 
 
 
 
— — — — 
— 
After making an axis error reset (refer to [3] in Section 
15.1), perform manual control operation (refer to 
Chapter 11) to move the axis to the other position in 
order that the upper limit signal (FLS) will turn ON. 
 
 
 
 
— — — — 
— 
After making an axis error reset (refer to [3] in Section 
15.1), perform manual control operation (refer to 
Chapter 11) to move the axis to the other position in 
order that the lower limit signal (RLS) will turn ON. 
 
 
 
 
 
 
 
 
 
 
 
— — — — 
— 
Check whether the stop commands (output 
signals/external inputs to QD75MH) are turned ON or 
OFF.  Turn OFF the ON commands. 
• Output signals to QD75MH 
Axis 1: Y4, Axis 2: Y5, Axis 3: Y6, Axis 4: Y7 
• External input 
Connectors for external device connection:  
Stop signals (STOP) 
After confirming the stop command status, cancel the 
error with an axis error reset.  Then turn ON a start 
signal. (Refer to Section 15.1[3]) 
 
 
 
 
— — — — 
— 
The PLC READY signal (Y0) is turned from OFF to ON 
when all BUSY signal is turned OFF. 
 
 
 
— — — — 
— 
Do not request the start when the axis operation state is 
other than "standby", "stop", and "step standby".