15 - 6 
MELSEC-Q
 
15   TROUBLESHOOTING 
 
15.2 List of errors 
The following table shows the error details and remedies to be taken when an error 
occurs. 
 
15.2.1 QD75MH detection error 
 
 
Classification 
of errors 
Error 
code 
Error name 
Error 
Operation status at error occurrence 
 
— 000 
(Normal 
status) 
— 
— 
 
001 Fault 
 
Fatal errors 
002  Internal circuit fault 
Hardware fault. 
The system stops. 
 
101 
PLC READY signal 
OFF during 
operation 
The PLC READY signal (Y0) is 
turned OFF during operation. 
The system stops with the setting 
(deceleration stop/sudden stop) of the 
detailed parameter 2 Sudden stop 
selection (stop group 2). 
(Note that the deceleration stop only 
occurs during the manual pulse 
generator operation.) 
 
 
 
 
 
 
 
102 
Servo READY signal 
OFF during 
operation 
The Servo READY signal is turned 
OFF during operation. 
The system stops immediately. 
 
 
 
103 
Test mode faults 
during operation 
The personal computer cannot 
communicate with the CPU unit. 
The system stops with the setting 
(deceleration stop/sudden stop) of the 
detailed parameter 2 Sudden stop 
selection (stop group 2). 
(Note that the deceleration stop only 
occurs during the manual pulse 
generator operation.) 
 
 
 
 
 
 
 
104 
Hardware stroke 
limit (+) 
The hardware stroke limit (upper limit 
signal FLS) is input turned OFF. 
 
 
 
 
105 
Hardware stroke 
limit (–) 
The hardware stroke limit (lower limit 
signal RLS) is input turned OFF. 
The system stops with the setting 
(deceleration stop/sudden stop) of the 
detailed parameter 2 Sudden stop 
selection (stop group 1).  
(Note that the deceleration stop only 
occurs during the manual pulse 
generator operation.) 
 
 
 
 
106 
Stop signal ON at 
start 
Start is requested when a stop signal 
is turned ON. 
The system does not start positioning. 
 
 
 
 
 
 
 
 
 
 
 
107 
READY OFF   ON 
during BUSY signal 
The PLC READY signal is turned 
from OFF to ON when BUSY signal 
is turned ON. 
• The QD75 READY signal (X0) is not 
turned ON. 
 
 
 
 
Common 
errors 
108  Impossible to start 
Start is requested when start is not 
possible in the axis operation state. 
The system does not start positioning.