15   TROUBLESHOOTING 
 
 
 
Classification 
of errors 
Error 
code 
Error name 
Error 
Operation status at error occurrence 
 
995 
Home position return 
(OPR) torque limit 
value error 
• The set range of the home position 
return (OPR) detailed parameter " 
Home position return (OPR) torque 
limit value" is outside the setting 
range. 
• The home position return (OPR) 
detailed parameter "Home position 
return (OPR) torque limit value" has 
exceeded the detailed parameter 1 
"Torque limit setting value". 
 
 
 
 
 
 
 
997 
Speed designation 
during home position 
(OP) shift error 
The set range of the home position 
return (OPR) detailed parameter 
"Speed designation during home 
position (OP) shift" is outside the 
setting range. 
 
 
 
 
Parameter 
setting range 
errors 
998 
Operation setting for 
incompletion of OPR 
setting error 
The set range of the home position 
return (OPR) detailed parameter 
"Operation setting for incompletion of 
OPR setting" is outside the setting 
range. 
The QD75 READY signal (X0) is not 
turned ON. 
 
1201 
Home position return 
(OPR) data incorrect 
The backup data for absolute position 
restoration is illegal. 
 
 
1203  Encoder error 1 
The change amount of the encoder 
current value during operation is 
shown below. 
"Change amount of the encoder 
current value/ 1.7 [ms] > Motor 180° " 
Check any time (both servo ON/OFF) 
after the servo amplifier is turned ON. 
 
 
 
 
 
 
 
Encoder 
errors 
1204  Encoder error 2 
The following equation is established 
during operation. 
“Encoder current value (encoder raw 
data) [PLS]   Feedback current value 
(data inside servo amplifier) [PLS] 
(number of encoder significant bits)” 
Check any time (both servo ON/OFF) 
after the servo amplifier is turned ON. 
Continue the operation.