Справочник Пользователя для Mitsubishi Electronics QD75MH2

Скачать
Страница из 838
 
 
 
4 - 16 
MELSEC-Q
4   INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT 
 
[Wiring examples using duct (incorrect example and corrected example)] 
 
Relay
Servo
amplifier
Noise source
PLC
QD
75
MH
Changed
Control panel
(Power system,
etc.)
Control panel
Servo
amplifier
Relay
Relay
Noise source
(Power system,
etc.)
Relay
Relay
Relay
PLC
Servo
amplifier
Servo
amplifier
The servo amplifiers are placed 
near the noise source. 
The connection cable between 
the QD75MH and servo amplifiers 
is too long.
The QD75MH and servo amplifiers 
are placed closely. The connection 
cable between the QD75MH and 
servo amplifier is separately laid 
from the power line (in this example, 
the cable is outside of the duct) and 
is as short as possible.
Wiring duct
Wiring duct
QD
75
MH