11.2 Periodic Inspection
 
11
MAINTENANCE AND INSPECTION
11.2  Periodic Inspection
The items that must be inspected one or two times every 6 months to 1 year are listed 
below.
When the equipment is moved or modified, or layout of the wiring is changed, also perform 
this inspection.
Table11.2 Periodic Inspection
Item
Inspection Item
Inspection
Judgment Criteria
Remedy
1
A
m
b
ien
t en
vi
ro
nm
en
t
Ambient temperature
Measure with a 
thermometer and a 
hygrometer.
0 to 55
When the sequencer is 
used in the board, the 
ambient temperature in the 
board becomes the 
ambient temperature.
Ambient humidity
5 to 95 %RH
Atmosphere
Measure corrosive gas.
Corrosive gas must not be 
present.
2
Power voltage
Measure a voltage across 
the terminals of 100/
200VAC.
85 to 132VAC
Change the power supply.
170 to 264VAC
3
In
st
all
atio
n
Looseness and rattling 
of module fixing screws
Try to further tighten screws 
with a screwdriver.
The module must be 
installed fixedly.
Retighten the screws.
If the CPU, or power 
supply module is loose, fix 
it with screws.
Adhesion of dirt and 
foreign matter
Check visually.
Dirt and foreign matter must 
not be present.
Remove and clean.
4
C
on
nec
tio
n
Looseness of terminal 
screws
Try to further tighten screws 
with a screwdriver.
Screws must not be loose.
Retighten the terminal 
screws.
Proximity of solderless 
terminals to each other
Check visually.
Solderless terminals must 
be positioned at proper 
intervals.
Correct.
Looseness of 
connectors
Check visually.
Connectors must not be 
loose.
Retighten the connector 
fixing screws.
5
Battery
Check "BAT." LED on the 
front face of the CPU 
module.
The LED must be Off.
If the LED is On, replace 
the battery.
Check the period after the 
purchase of the battery.
The period must be five 
years or less.
If the battery is used for 
more than 5 years, replace 
the battery.
Check in the monitoring 
mode of GX Developer that 
SM51 or SM52 is turned 
OFF.
SM51 or SM52 must be 
OFF.
If SM51 or SM52 is ON, 
replace the battery.
6
Number of writes to 
standard ROM
Check the values of SD232 
and SD233 in the monitoring 
mode of GX Developer.
The number of writes to the 
standard ROM must be 
100,000 times or less.
If the number of writes to 
the standard ROM 
exceeds 100,000 times, 
replace the CPU module.
7
Clock
Check the current time at 
the clock setting of GX 
Developer.
There is no time lag 
between the time checked 
at the time setting of GX 
Developer and the actual 
time.
Change the time at the 
time setting of GX 
Developer.