TROUBLESHOOTING
12.2 Troubleshooting Flowchart
12.2.8 When the "USER" LED turns on
12
 - 14
9
EM
C AN
D
 L
O
V
O
LT
AG
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND 
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
 AND 
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
 A
PPE
NDICES
 INDEX
 
 
Remark
The following causes are possible when the "ERR." LED of the CPU module 
flashes at programmable controller power-on.
12.2.8  When the "USER" LED turns on
If the "USER" LED turns on, follow the steps described below.
The "USER" LED turns on when an error is detected by the annunciator (F) turns on.
If the "USER" LED turns on, monitor the special relay SM62 and the special registers 
SD62 to SD79 in the monitor mode of GX Developer.
 • When M62 has turned ON
The annunciator (F) is ON.
Using SD62 to SD79, check the error cause.
Eliminate the error cause after confirming it.
The "USER" LED can be turned off by:
 • Making a reset with the RUN/STOP/RESET switch.
 • Canceling Errors with the special relay and the special register 
(
Table12.2 Error messages and causes
Error Message
Cause
Corrective Action
MODULE LAYOUT 
ERROR
(Error code: 2125)
The multiple CPU system is 
configured.
Remove all CPU modules other 
than the safety CPU module from 
the base unit.
Modules other than intelligent 
function modules are mounted on 
the base unit.
Remove all modules other than 
intelligent function modules from 
the base unit.
CC-LINK PARAMETER 
ERROR
(Error code: 3105)
The CC-Link Safety master 
module mounted on the base unit 
is not set as a master station.
Set the CC-Link Safety master 
module as a master station.
NETWORK PARAMETER 
ERROR
(Error code: 3100)
• The MELSECNET/H module 
mounted on the base unit is not 
set as a PLC to PLC network 
normal station.
• The number of CC-Link IE Field 
Network master/local modules 
(with safety functions) actually 
mounted is different from that is 
set in Network parameter for 
CC-Link IE Field Network.
• Set the MELSECNET/H module 
as a PLC to PLC network 
normal station.
• Mount or remove the CC-Link 
IE Field Network master/local 
modules (with safety functions) 
so that the number matches 
that is set in Network 
parameter.
NETWORK PARAMETER 
ERROR
(Error code: 3103)
The number of Ethernet modules 
actually mounted is different from 
that is set in Network parameter 
for Ethernet.
Change either the number of 
modules or parameter setting so 
that they become the same.