12
 - 17
12.2 Troubleshooting Flowchart
12.2.11 Flowchart for when a program cannot be written
12
TROUBLESHOOTING
12.2.11  Flowchart for when a program cannot be written
The following shows the flowchart for when programs cannot be written in the CPU 
module.
 * 1:  If the password registration cannot be canceled due to the loss of 
password, initialize the PLC memory with GX developer.
The PLC memory initialization initializes the memory of the CPU 
module (i.e. deletes all information in the CPU module) and resets 
the memory to the factory default.
 GX Developer Operating Manual (Safety Programmable 
            Controller)
Figure 12.7  Flowchart for when a program cannot be written
NO
YES
NO
NO
YES
YES
YES
YES
A program cannot be written to the CPU 
Completed
Can a program be 
written?
Has the password 
registered?
Format program memory.
Cancel the password using GX 
Developer. *1
Perform the following.
    Organize files.
    Confirm memory space.
    Confirm the writing destination. 
Can a program be 
written?
Can a program be 
written?
Can the program be 
written?
NO
Hardware error
Please consult your local Mitsubishi 
representative, explaining a detailed 
description of the problem.
NO
NO
Turn on power supply again and 
initialize the PLC memory. Register 
the CPU access password.