TROUBLESHOOTING
12.3 Error Code List
12.3.4 Error code list (2000 to 2999)
12
- 30
9
EM
C AN
D
L
O
W
V
O
LT
AG
E
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
AND
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
A
PPE
NDICES
INDEX
Error
Code
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
2000
• Intelligent function module
information at power ON are
changed.
changed.
• During operation, Intelligent function
module are not installed properly or
installed on the base unit.
installed on the base unit.
Read the common information of the
error using the GX Developer, and
check and/or change the module that
corresponds to the numerical values
(module number) there.
Alternatively, monitor the special
registers SD 150 to SD 153 at a GX
Developer, and change the fuse at the
output module whose bit has a value of
"1".
error using the GX Developer, and
check and/or change the module that
corresponds to the numerical values
(module number) there.
Alternatively, monitor the special
registers SD 150 to SD 153 at a GX
Developer, and change the fuse at the
output module whose bit has a value of
"1".
QS
2100
• In the parameter I/O allocation
settings, an Inteli (intelligent function
module) was allocated to a location
reserved for an I/O module.
module) was allocated to a location
reserved for an I/O module.
• In the I/O assignment setting of the
PLC parameter dialog box, the
number of points assigned to the
intelligent function module is less
than the number of points of the
mounted module.
number of points assigned to the
intelligent function module is less
than the number of points of the
mounted module.
Reset the parameter I/O allocation
setting to conform to the actual status of
the intelligent function module.
setting to conform to the actual status of
the intelligent function module.
QS
2106
• More than three CC-Link Safety
master modules are mounted.
• More than two CC-Link IE Controller
Network modules are mounted.
• More than two MELSECNET/H
modules are mounted.
• More than two Ethernet modules are
mounted.
• A module that the Safety CPU
module cannot recognize has been
mounted.
mounted.
• More than two CC-Link IE Field
Network master/local modules (with
safety functions) are mounted.
safety functions) are mounted.
• Mount two or less CC-Link Safety
master modules.
• Mount either only one CC-Link IE
Controller Network module or
MESECNET/H module.
MESECNET/H module.
• Mount only one Ethernet module.
• Mount a module supported in the
• Mount a module supported in the
Safety CPU module.
• Mount only one CC-Link IE Field
Network master/local module (with
safety functions).
safety functions).
QS