Справочник Пользователя для Mitsubishi Electronics QSPCU

Скачать
Страница из 224
12
TROUBLESHOOTING
12.4 Clearing an error
 
12
 - 66
9
EM
C AN
D
 L
O
V
O
LT
AG
DI
RE
C
T
IV
E
S
10
LO
A
D
ING A
ND 
INS
TA
LLA
T
ION
11
M
A
INT
E
NANCE
 AND 
IN
SP
ECT
IO
N
12
T
R
O
U
BL
ES
HO
O
T
IN
G
 A
PPE
NDICES
 INDEX
 
 
To cancel the errors, follow the steps shown below.
1) Read the special register SD81 with GX Developer and confirm the cause of 
the continuation error that currently occurs in the CPU module.
2) Eliminate the cause of the error.
3) Store the error code to be canceled in the special register SD50.
4) Energize the special relay SM50 (OFF   ON).
5) Read the special register SD81 with GX Developer again and confirm that the 
bit corresponding to the canceled continuation error is turned OFF.
6) Turn the special relay SM50 OFF.
  
After the CPU module is reset by the canceling of the error, the special relays, special 
registers, and LEDs associated with the error are returned to the status under which 
the error occurred.
If the same error occurs again after the cancellation of the error, it will be registered 
again in the operation/error history.
When multiple enunciators(F) detected are canceled, the first one with No. F only is 
canceled.
If the canceling of errors is performed when multiple continuation errors are occurring, 
the LED indication and error information of the CPU module operate as follows.
Refer to the following manual for details of error canceling.
QSCPU User's Manual (Function Explanation, Program Fundamentals)
Error Canceling Status
LED Indication *1
("ERR." LED, "BAT." LED, 
"USER" LED)
Error Information
(SM0, SM1, SM5, SM16, SD0 
to 26)
Before canceling errors
On
The error information of the 
continuation error that 
occurred last is stored.
The error which occurred last 
is cancelled.
(The continuation error that is 
not canceled remains.)
On
Returned to the status without 
error.
Errors other than the 
continuation error that 
occurred last are cancelled.
(The continuation error that is 
not canceled remains.)
On
No change
(The error information that 
occurred last is retained.)
All the continuation errors are 
cancelled.
Off
No error
*1: 1)
Error code: When 1600 (BATTERY ERROR) occurs, only "BAT." LED turns on.
Error code: When canceling the error code 1600, "BAT." LED turns off.
2)
Error code: When 9000 (F****) occurs, only "USER" LED turns on.
Error code: When canceling the error code 9000, "USER" LED turns off.