2.1.1  Precautions for system configuration
(1) Modules mountable on the main base unit
Table2.3 lists the modules that can be mounted on the main base unit.
The number of mounted modules and functions are restricted depending on the 
module type.
(2) Module/Unit Replacement
Replace the module or unit according to the following replacement cycle.
Table2.3 Modules mountable on the main base unit
Module
Model
Number of modules 
mounted in one system
Remarks
CPU module
• QS001CPU
Only one
---
Power supply module
• QS061P-A1
• QS061P-A2
Only one (only one of the module 
models)
---
CC-Link Safety master 
module
• QS0J61BT12
Up to two
---
CC-Link IE Field Network 
master/local module (with 
safety functions)
• QS0J71GF11-T2
Only one
---
CC-Link IE Controller Network 
module
• QJ71GP21-SX
• QJ71GP21S-SX
Only one (only one of the models 
among CC-Link IE Controller 
Network modules and MELSECNET/
H modules)
• Serial number (first five digits): 
“10041” or later
• Function version: D or later
MELSECNET/H module
• QJ71LP21-25
• QJ71LP21S-25
• QJ71LP21G
• QJ71LP21GE
• QJ71BR11
• Serial number (first five digits): 
“08102” or later
• Function version: D or later
Ethernet module
• QJ71E71-B2
• QJ71E71-B5
• QJ71E71-100
Only one (only one of the module 
models)
---
Blank cover
• QG60
Up to four
---
Table2.4 Module/Unit Replacement
Module/Unit
Replacement Cycle
Safety power supply module
5 years
Safety CPU module
10 years
Safety main base unit
10 years
CC-Link Safety master module
10 years
CC-Link IE Field Network master/local module (with 