Справочник Пользователя для Mitsubishi Electronics QSPCU

Скачать
Страница из 224
3
GENERAL SPECIFICATIONS
 
 
3
 - 1
1
O
VE
R
VI
EW
2
S
YST
EM
 
CONF
IGURA
T
ION
3
GENERA
SPE
CIF
ICA
T
IONS
4
CPU M
O
DUL
E
5
PO
W
E
R SUP
P
LY
 
M
O
DUL
6
B
ASE
 UNI
7
BA
TT
ER
Y
8
CPU M
O
DUL
E ST
ART
-
UP P
ROCEDURE
S
CHAPTER3  GENERAL SPECIFICATIONS
The performance specifications of QS series programmable controllers are shown in Table3.1.
*1
: This indicates the section of the power supply to which the equipment is assumed to be connected between the public 
electrical power distribution network and the machinery within premises. Category II applies to equipment for which 
electrical power is supplied from fixed facilities. The surge voltage withstand level for equipment with the rated voltage 
of up to 300V is 2500V.
*2
: This index indicates the degree to which conductive material is generated in terms of the environment in which the 
equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by 
condensing may be expected occasionally.
*3
: Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m. 
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local 
Mitsubishi Electric representative.
Table3.1 General specifications
Item
Specifications
Operating ambient temperature
0 to 55
Storage ambient temperature
-40 to 75
 
Operating ambient humidity
5 to 95%RH, non-condensing
Storage ambient humidity
Vibration resistance
Compliant
with JIS B
3502 and
IEC 61131-2
Frequency
Constant
acceleration
Half 
amplitude
Sweep count
Under
intermittent
vibration
5 to 8.4Hz
----
3.5mm
10 times
each in X, Y,
Z directions
8.4 to 150Hz
9.8m/s
2
----
Under
continuous
vibration
5 to 8.4Hz
----
1.75mm
----
8.4 to 150Hz
4.9m/s
2
----
Shock resistance
Conforming to JIS B 3502 and IEC 61131-2 (147 m/s
2
, duration of action 11ms, 3 times 
each in 3 directions X, Y, Z by sine half-wave pulse)
Operating atmosphere
No corrosive gases
Operating altitude
*3
0 to 2000m
Installation location
Inside a control panel
Overvoltage category 
*1
II or less
Pollution degree 
*2
2 or less
Equipment class
Class I