Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
86
Table 29
Liebert DataMate
™
, Liebert Mini-Mate2
™
- Input and Holding - MM2
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Temperature
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Cooling
—
40003
1
—
1=On / 0=Off
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
Dehumidification
—
40006
1
—
1=On / 0=Off
Econ-o-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Alarm Points
Communications
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Head Pressure 1
—
40289
1
—
Bit 3
Loss of Airflow
—
40289
1
—
Bit 5
Standby Glycol Unit On
—
40289
1
—
Bit 6
Change Filters
—
40289
1
—
Bit 8
High Temperature
—
40289
1
—
Bit 9
Low Temperature
—
40289
1
—
Bit 10
High Humidity
—
40290
1
—
Bit 0
Low Humidity
—
40290
1
—
Bit 1
Humidifier Problem
—
40290
1
—
Bit 2
Smoke Detected
—
40290
1
—
Bit 8
Loss of Water Flow
—
40290
1
—
Bit 9
Standby Unit On
—
40290
1
—
Bit 10
Short Cycle
—
40291
1
—
Bit 1
Loss of Power
—
40291
1
—
Bit 2
Local Alarm 1
—
40291
1
—
Bit 6
Local Alarm 2
—
40291
1
—
Bit 7
Local Alarm 3
—
40291
1
—
Bit 9
Local Alarm 4
—
40291
1
—
Bit 10
Run Hours (View)
Compressor 1
Compressor 1
—
40019
1
—
—
Fan Motor
—
40020
1
—
—
Humidifier
—
40021
1
—
—