Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
86
Table 29
Liebert DataMate
, Liebert Mini-Mate2
 - Input and Holding - MM2
Controller
MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units
Status Points (View)
Temperature
40001
1
Humidity
40002
1
Cooling
40003
1
1=On / 0=Off
Heating
40004
1
1=On / 0=Off
Humidification
40005
1
1=On / 0=Off
Dehumidification
40006
1
1=On / 0=Off
Econ-o-Cycle
40007
1
1=On / 0=Off
Stages
40008
1
% Capacity
40009
1
Alarm Points
Communications
40289
1
Bit 0
Local Off
40289
1
Bit 1
Remote Off
40289
1
Bit 2
High Head Pressure 1
40289
1
Bit 3
Loss of Airflow
40289
1
Bit 5
Standby Glycol Unit On
40289
1
Bit 6
Change Filters
40289
1
Bit 8
High Temperature
40289
1
Bit 9
Low Temperature
40289
1
Bit 10
High Humidity
40290
1
Bit 0
Low Humidity
40290
1
Bit 1
Humidifier Problem
40290
1
Bit 2
Smoke Detected
40290
1
Bit 8
Loss of Water Flow
40290
1
Bit 9
Standby Unit On
40290
1
Bit 10
Short Cycle
40291
1
Bit 1
Loss of Power
40291
1
Bit 2
Local Alarm 1
40291
1
Bit 6
Local Alarm 2
40291
1
Bit 7
Local Alarm 3
40291
1
Bit 9
Local Alarm 4
40291
1
Bit 10
Run Hours (View)
Compressor 1 
40019
1
Fan Motor
40020
1
Humidifier
40021
1