20      Chapter 2  Installation 
ACTURA Flex 48330
 
Power System  User Manual 
2.3.2  Connection Of Load Cables 
Loads are connected to the MCB with suitable capacity to avoid their failure to 
function in the case of overload. The capacity of the MCBs is recommended to be 
about 1.5 times of the peak value of the load capacity. The load circuit breakers are 
shown in Figure 1-7. The circuit breakers can be ABB or CBI circuit breakers. 
We take the CBI circuit breakers of 13mm for example to illustrate the load cable 
connection, as shown in the Figure 2-10. 
High-priority load busbar 
Battery –48V busbar 
Low-priority 
load busbar 
connected with 
low-priority load 
busbar 
connected with 
high-priority load 
busbar 
 
Figure 2-10    Connection of load cables 
Explanation: the load MCBs and battery MCBs can be configured flexible according 
to the actual requirements. Their setting range is shown in the following table. 
Table 2-3  Configuration number of load MCBs and battery MCBs 
Busbar type 
Max. load number   
Note 
Battery -48V busbar 
0~5 
High-priority load busbar 
0~19 
Low-priority load busbar 
0~28 
Total number of the load should not 
exceed 20 with 18mm-width MCB or 
not exceed 28 with 13mm-width MCB. 
 
Cable connection to MCB: strip the power cable end, crimp-connect the copper 
core to an H terminal, See Figure 2-4 for the cable mounted with a H terminal. After 
attaching the H terminal to the cable, insert the cable into the wiring hole of the 
MCB, then tighten the screw to fix the copper core, as shown in Figure 2-11: 
 
Cable 
H terminal
 
Figure 2-11    Cable connection to MCB