Chapter 5  Operating SCU      59 
ACTURA Flex 48330
 
Power System  User Manual 
Table 5-12    Charging management parameter value description 
Parameter  
Range 
Default
Value description 
Float  
53.5V 
In the FC state, all rectifiers output 
voltage according to the set “Float”   
Boost  
42V ~ 58V 
56.4V 
In the BC state, all rectifiers output 
voltage according to the set “Boost” 
The “Boost” must be 
higher than the “Float” 
Limit (current 
limit) 
0.1 ~ 0.25C
10
 0.1C
10
 
When the monitoring module detects that the battery charging 
current is higher than the “Limit”, it will control the current of the 
rectifiers, through which it can limit the battery charging current.   
C
10
 is the battery rated capacity, generally set to 10 ~ 20% of the 
rated capacity of one battery string.   
Over (over current 
point)  
0.3C
10
 ~ 1.0C
10
 0.300C
10
When the monitoring module detects that the battery charging 
current is higher than the “Over”, it will raise the battery charge 
over-current alarm.   
Automatic Boost 
Select “Y”, and BC will be conducted when conditions allow   
Cyclic Boost 
Yes, No 
Cyclic Boost 
Interval 
48 ~ 8760h 
2400h 
Cyclic Boost Time  30 ~ 2880min 
720min 
Select “Y”, and the monitoring module will control the system to 
enter the Cyclic Boost when the FC time reaches the “Cyclic Boost 
Interval”. The battery charging voltage is the preset “Boost”, and 
the time is the preset “Cyclic Boost Time”   
To Boost Current    0.50 ~ 0.80C
10
 0.06C
10
 
To Boost 
Capacity 
0.1 ~ 0.95 
0.80 
The monitoring module will control the system enter the BC state 
when the battery capacity decreases to the value of “To Boost 
Capacity”, or when the charge current reaches the “To Boost 
Current”. The charge voltage will be the “Boost”.   
Constant BC Curr  0.02 ~ 0.99C10  0.01C
10
 
Duration (of 
constant BC) 
30 ~ 1440min    180min 
The system in the BC state will enter the FC state when the charge 
current decreases to the “Constant BC Curr” and after the 
“Duration”. The battery charge voltage then will be the “Float”.   
Boost Limit 
60 ~ 2880min 
1080min
To ensure safety, the monitoring module will forcefully control the 
system to enter the FC state if during the BC state, the BC time 
reaches the “Boost Limit”, or abnormalities occur (such as AC 
failure and battery route faulty, etc.). 
 
3. The BC/FC switchover diagram is shown below: 
Battery charge current 
bigger than "To BC Current"
Battery capacity smaller 
than "To BC Capacity"
Abnormal situation
FC
BC
Constant BC 
time-up
Charge current 
smaller than 
"Constant BC 
Curr"
Constant 
BC
BC time longer than 
"BC LVD Time"
FC time longer than "Scheduled BC Interval"
 
Figure 5-2    BC/FC switchover diagram