Chapter 5  Operating SCU      61 
ACTURA Flex 48330
 
Power System  User Manual 
2. The value description of the parameters is listed below: 
Table 5-13    Value description of the battery test parameters 
Parameter  
Range 
Default 
Value description 
Battery test 
voltage  
43.1V ~ 
57.9V 
45.2V 
Battery test time  5 ~ 1440min  300min 
Test End Cap 
(capacity) 
0.01C
10
 ~ 
0.95C
10
 
0.7C
10
 
The monitoring module can do battery test, and record 10 sets of 
test data (accessible only through the host). The battery test has to 
be started manually, then monitoring module will control the rectifier 
output voltage, make it lower than the battery voltage, and the 
battery discharge will begin. Monitoring module will stop the test if 
the battery voltage reaches the “Battery test voltage”, or the 
discharge time reaches “Battery test time”, or the battery capacity 
reaches “Test End Cap”. Afterwards, it will restore the rectifier 
output voltage to the normal FC voltage, begin the battery charge 
and switch the system to battery auto-management. Meanwhile the 
test start time/voltage and end time/voltage and battery remaining 
capacity will be recorded. The records can be queried through the 
host.  
During the battery test, if abnormalities occur, the monitoring 
module will stop the battery test automatically.   
Scheduled Test  Y, N 
Planned Test 1 
00:00, Jan. 1
st
 
Planned Test 2 
00:00, April 1
st
 
Planned Test 3 
00:00, July 1
st
 
Planned Test 4 
Month,day, 
hour  
00:00, Oct. 1
st
 
When the parameter “Scheduled Test” is set to “Y”, the monitoring 
module will test the battery according to the 4 sets of test time. You 
can set at most 12 sets of test time through the host.   
Alarm Current    1A ~ 100A 
10A 
ShortTest Cycle  24h ~ 8,760h  720h 
ShortTest 
Duration 
1 ~ 60min 
5min 
If the battery have not discharged within the “ShortTest Cycle”, the 
monitoring module will start a short test, whose operation time is 
set by the parameter “ShortTest Duration”. By the end of the test, if 
the difference in the discharge currents of batteries is bigger than 
the “Alarm Current”, the battery discharge imbalance alarm will be 
raised. This alarm will automatically end after 5min of delay. Also 
you can end it by confirming it.   
StableTest 
Enable 
Y, N 
 
StableTest 
Current 
0 ~ 9999A 
9999A 
The stable test is conducted with constant battery current, whose 
value is set through the parameter “StableTest Current”. If the 
parameter “StableTest Enable” is set to “Y”, and the test will be 
started once the battery satisfies the test condition   
 
3. The schematic diagram of the test function is shown below:   
Battery 
Auto-management
Manually start 
battery test
Rectifier output 
voltage lower than 
battery voltage
Battery 
discharges
Rectifier hot 
standby
"Test End Voltage" 
is reached
"Test End Cap" is 
reached
"Test End Time" is 
reached
 
Figure 5-3  Schematic diagram of the test function