Справочник Пользователя для Emerson 48330

Скачать
Страница из 96
Chapter 5  Operating SCU      69 
ACTURA Flex 48330
 
Power System  User Manual 
Parameter  
Range  
Default
Value description   
Operator 
level or 
above 
System 
Type 
24V/75A/500/NONE  
24V/75A/500/MAN  
24V/75A/500/AUTO 
24V/50A/500/NONE 
24V/50A/500/MAN  
24V/50A/500/AUTO 
48V/50A/500/NONE  
48V/50A/500/MAN 
48V/50A/500/AUTO  
48V/50A/300/NONE  
48V/50A/300/MAN 
48V/50A/300/AUTO 
48V/30A/300/NONE  
48V/30A/300/MAN 
48V/30A/300/AUTO 
48V/30A/100/NONE 
48V/30A/100/MAN 
48V/30A/100/AUTO 
48V/15A/100/NONE 
48V/15A/100/MAN 
48V/15A/100/AUTO 
48V/100A/SET/NON 
48V/100A/SET/MAN 
48V/100A/SET/AUT 
48V/50A/SET/NONE 
48V/30A/SET/NONE 
This parameter has been set according to the actual situation 
upon delivery and needs not to be changed. However, when a 
new monitoring module is used, its “System Type” should be 
set according to the actual situation.   
After this parameter is changed, the monitoring module will 
restart automatically, and other parameters of the monitoring 
module will be changed to the defaults of the corresponding 
system type. You should change some parameters according 
to the actual situation.     
Change 
Password 
User, Operator, Admin 
The password can be 6 digits long at most. If it is shorte than 6 
digits, end it with a “#”   
Con Alarm 
Voice  
3min, 10min, 1h, 4h, 
constant  
Contstant  The period that an alarm sound will last 
Serial 
The production serial No. of the monitoring module. This parameter cannot be changed 
SW Ver 
The software version No. of the monitoring module. This parameter cannot be changed 
Administrator 
Set Enable
Reflecting the jumper status of a hardware switch within the monitoring module. If this 
parameter is set to ”N”, you are not allowed to use the jumper, nor change any 
parameter except the battery management mode. The maintenance over the monitoring 
module will not be affected   
 
5. The model description is shown below:   
48V    /      30A      /     300     /     NONE
No AC data acquisition
 board
System shunt coefficient: 
100/300/500/SET
Rectifier rated output current: 
15A/30A/50A/75A/100A
Rectifier rated output 
voltage: 48V/24V
 
Figure 5-4    System model description