Chapter 5  Operating SCU      71 
ACTURA Flex 48330
 
Power System  User Manual 
Use “
” or “
” to select one page or one of the parameters, and “
” or “
” to 
select the parameter value. Press “ENT” to confirm and save. 
3. After setting the “Set DI Name” and confirming it, the system will prompt you to 
name the DI: 
 DI Name 
Digital 1 
 
 
 
 
Use “
” or “
” to change the number, and “
” or “
” to move the cursor left or 
right. Press “ENT” to confirm.   
4. The value description of the parameter is listed below:   
Table 5-20    Value description of alarm settings 
Parameter  
Range  
Default 
Value description   
Alarm Type 
56 names of alarm 
events  
Select those alarm events whose levels and relate relays 
should be reset 
Level 
Critical, Major, 
Observation, None 
There are different audible/visual alarm modes and callback 
modes for alarm events of different levels   
Relate Relay 
Empty, No.1 ~ 8 
Alarms of 
different 
types have 
different 
levels and 
different 
Relate 
Relays  
“Empty”: The corresponding dry contact will not output alarm 
information upon an alarm event   
“No. 1 ~ 8”: There will be a dry contact in the range of No.1 ~ 
8 that outputs the alarm information upon an alarm event   
DI No. 
No. 1 ~ 8 
The 8 corresponding connecting terminals, 
queued up in the order that the hardware 
switches are put   
Alarm Mode 
High, Low 
Low 
“High”: alarm upon high level;   
“Low”: alarm upon low level.   
Set according to the actual situation 
Set DI Name 
1# ~ 8# 
1# 
Serial No. of the connecting terminal for DI 
input  
DI Name 
Figures or letters, 
10 at most 
Digital 
When there are DI alarms, this parameter 
shows the alarm name you have actually 
defined. In the system with an AC sampling 
board, you can define by yourself the DIs of 
routes No.7 and No.8.   
In the system without an AC sampling board, 
you can define all DIs   
Effective 
only to 
self-defined 
DI alarms   
Clear His Alarm   Y, N 
“Y”: Delete historical alarms 
Block Alarm 
Y, N 
“Y”: The active alarms will not be sent to the host (valid in 
EEM protocol)