Chapter 3 - Handling of Control Panel CDP 31x
 
 
 
 
DCS 500B / DCP 500B Operating Instructions 
IV A
  
3 - 15 
 
3.14 Running the Drive 
 
Operational Com-
mand Keys 
Operational commands can be given from the Control Panel 
CDP31x every time when the status row is displayed. Operational 
commands include START and STOP of the the drive, controlling 
the main contactor and adjusting the reference.  
 
CAUTION! 
To be able to give operational commands from the 
CDP31x, the selected control location must be the 
Control Panel. The control location can be changed 
by means of LOC/REM key to LOCAL mode.  
 
If LOC is activated some of the  
binary inputs are no longer functioning.  
 
Take care that the drive is engineered to allow opera-
tion with 
LOCAL mode
  
 
Control  
Panel Key 
Name of Key 
Function 
LOC
REM
 
LOCAL /  
REMOTE 
To select LOCAL (= 
CDP31x
) or REMOTE  
(= ext. control system) operation. 
 
START 
Starts the drive, when in LOCAL mode. 
 
STOP 
Stops the drive, when in LOCAL mode.  
 
ON 
Main contactor closing control, when in 
LOCAL mode. 
 
OFF 
Main contactor opening control, when in 
LOCAL mode. 
 
Running the DC- 
Drive from  
the 
CDP31x
 
 
E
nsure safety before you start the drive test!
 
 
M
 
 
  Select LOCAL mode 
(LOCAL = 
CDP31x
by pressing 
LOC/REMOTE key. 
  Close (switch on) the main contactor by pressing the ON key 
  Start the drive by pressing the START key. Motor will now ac-
celerate to the value of the reference. 
  Direction of rotation can be changed by giving the opposite po-
larity reference value in case of 4Q drive. 
  Stop the drive by pressing the STOP key. Motor will decelerate 
to zero speed. (depending on the STOP MODE) 
  Finally open (switch off) the main contactor by pressing the  
 
OFF key. 